Voltage Drop Calculator

Load, length, and gauge in — volts at the far end out.

Circuit & run

Length is panel to load one way — the formula doubles it for the round trip.

Drop

5.93 volts lost

4.9% drop · 114.07 V at the load

Over the 3% note — consider 8 AWG

NEC note≤ 3% branch · ≤ 5% total (recommendation)
Min. gauge for 3%8 AWG
THE RUN — VOLTS IN, VOLTS OUT PANEL 120 V 12 AWG COPPER LOAD 114.07 V 100 FT ONE WAY DROP AGAINST THE 3% NOTE 3% 10% SCALE
Formula: VD = 2 × K × I × L ÷ CM Longer run or lower voltage → fatter wire

This checks voltage drop only — not ampacity or code. The wire must first be sized to the breaker per the NEC ampacity tables, and local code governs. Have a licensed electrician confirm before pulling anything.

Summary + link — paste into a quote or text

Estimates, not advice. This calculator exists to give you a working idea of the materials a job needs and a rough cost — not numbers to commit money or construction to. Check the figures yourself, or with an appropriately qualified professional, before you order, quote, or build. Read the full disclaimer

How this voltage drop calculator works

Wire is a resistor, and long runs spend voltage on it. The classic estimating formula prices that loss from four numbers:

VD = 2 × K × I × L ÷ CM · K: 12.9 copper / 21.2 aluminum
% drop = VD ÷ system volts · NEC note: ≤ 3% branch, ≤ 5% total

Worked example: voltage drop on a 100 ft run

15 A over 100 ft of 12 AWG copper (6,530 CM): VD = 2 × 12.9 × 15 × 100 ÷ 6,530 = 5.93 V4.9% of 120 V, leaving 114.07 V at the load. Over the 3% note: the first listed gauge that passes is 8 AWG.

What wire size for the run? — 3% chart

Table 1 — Min. copper gauge inside 3% · 120 V, 15 A
One-way runGauge
25 ft14 AWG
50 ft12 AWG
75 ft10 AWG
100 ft8 AWG
150 ft8 AWG
200 ft6 AWG
Generated by this calculator's engine — drop only; ampacity is a separate, binding check.
Table 2 — Conductor areas (NEC ch. 9)
GaugeCircular mils
14 AWG4,107
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
Each two gauge sizes ≈ doubles the copper.

Voltage drop FAQ

How do I calculate voltage drop?

The standard 2-wire estimating formula: VD = 2 × K × I × L ÷ CM, with K = 12.9 for copper, I the amps, L the one-way feet, and CM the wire’s circular mils. The default 15 A over 100 ft of 12 AWG drops 5.93 V — 4.9% of a 120 V circuit.

What is an acceptable voltage drop?

The NEC’s informational note recommends no more than 3% on a branch circuit and 5% total with the feeder — a recommendation for performance, not a code mandate in most cases. Motors, compressors and electronics are why you honor it anyway.

What size wire do I need for a 100 ft run?

For 15 A at 120 V, 8 AWG copper is the first listed gauge inside 3% at 100 ft — two sizes fatter than the 14 AWG that ampacity alone would allow. Distance, not just load, sizes long runs; the chart below shows the crossover lengths.

Does voltage drop matter less at 240 V?

Yes — the same volts lost are half the percentage at 240 V, which is why long feeders to shops and barns usually run 240. Low-voltage systems invert that: at 12 V even short runs drop brutal percentages, as landscape-lighting installers learn fast.

Is aluminum wire worse for voltage drop?

Aluminum’s K is 21.2 against copper’s 12.9, so it needs about 64% more circular mils for the same drop — typically two AWG sizes up. It still wins on cost for big feeders, which is why service conductors are commonly aluminum.

Does this tell me the wire is code-legal?

No — it checks voltage drop only. The conductor must first be sized to the breaker per the NEC ampacity tables, with derating, termination ratings and local amendments on top. Treat the result as planning math and have a licensed electrician confirm.

Embed this voltage drop calculator on your site

Run the voltage drop calculator on your own site, free. Paste the snippet where you want it; the visible credit link is the only condition.

More jobsite calculators

Drop −5.93 V 4.9% 114.07 V at the load